A to Z of Services

A B C D E F G H I J K L M

N O P Q R S T U V W X Y Z

 
  Home > Planning and Building Control > Building Control > Technical Guidance > Loft Conversion to a 2 Storey Dwelling

Loft Conversion to a 2 Storey Dwelling

Overview

If you intend to convert an existing loft space into additional rooms you will need to apply for building regulation approval. You may also need planning permission if you live in a conservation area, area of outstanding natural beauty or a listed building and/or are installing a dormer window or rooflight. It is strongly advised that you speak with the planning department before undertaking such work.

 

This guidance deals with the technical points of building regulations which most often cause difficulties - if you cannot find ways of dealing with them, it may not be possible to convert your loft at all.

 

Latest Building Regulations Requirements

From 6 April 2007 there have been significant changes to requirements for loft conversions. Most of the reduced standards that have existed for a number of years have now been removed and loft conversions to a 2 storey house are to be treated in similar way to a new 3-storey house.

 

As a result more onerous conditions apply requiring the formation of a fire resistant protected escape route out from the loft to the dwelling’s final exit, in order to prevent occupants been trapped in a fire.

 

You now cannot to rely on escape windows to make safe escape, as it is considered that you will be able to reach the ground floor internally via the fire protected stairway.

 

The upper storeys must by served by a fire protected stairway (protected at all levels) which either:-

 

a. at ground floor level discharges to a hall served by an external door, or

 

b. there must be at least two separate escape routes available to an external door - separated by fire resistant construction and fire doors.

 

If you have an open plan staircase it will therefore need to be enclosed.

 

The protected stair enclosure should be enclosed in a minimum 30-minute fire resisting construction to protect the escape route for the occupants to make a safe escape.

 

All doors opening onto the protected stair are to be FD20 or E20 fire resisting doors.

 

One concession is that there is no need to fit self-closing devices to any fire doors.

 

You must ensure that the new loft access stair is an extension of the existing stair enclosure to avoid the creation of inner rooms. The new stair to the second floor cannot be enclosed within a first floor habitable room such as a bedroom.

 

The new stair has to continue up in the existing stair enclosure, in which case the fire door and additional separating structure will be at the top floor level. Alternatively if there is only one room in the loft space, the loft stair can be contained within the second floor room itself and a fire door provided at the base of stair landing position, where it exits onto the existing first floor landing.

 

Where the existing house is open-plan, it will be necessary either to provide a new 30-minute fire resistant partition with fire doors to enclose and extend the escape route to a final exit, or provide sprinkler protection to the open-plan area in accordance with BS9251: 2005, in conjunction with a fire resisting partition and door (FD20 / E20) positioned to separate the ground floor from the upper storeys. This door should be so arranged to allow the occupants of the loft room(s) to access an escape window at first floor level in event of a fire in the open-plan area. Cooking facilities must, however, in all cases be separated from the open-plan area with 30 minute fire-resisting construction.

 

Rooms within the loft should be designed so that there are no inner rooms i.e. where escape can only be made by passing through another room, unless the inner room is a dressing room, a bathroom, a shower room or a w.c.

 

Smoke Detection

Mains powered and rechargeable battery backed up smoke detectors must be installed on each storey in accordance with BS5839-6: 2004 – Grade D - category LD3 standard.

 

All detectors must be interlinked together so that all sound even if only one is triggered and must be placed in the circulation spaces / protected stairway within 7.5m of every habitable room door. If, however, due to the layout of the loft there is no circulation space, a smoke detector should be fitted in the loft room itself.

 

Smoke detectors should be mains powered to a single independent circuit on the dwellings mains consumer unit or a single regularly used local lighting circuit. A means of isolating power to the smoke alarms should be provided without isolating the lighting.

 

Detectors are to be positioned so that they can be reached for maintenance and testing i.e. not over stairs etc.

 

If floor area of the loft exceeds 200 square metres, the building will be considered to be a ‘large house’ and the fire detection system will need to be improved:-

 

a. large dwellings of 2 storeys (excluding basements) to have fire detection / alarm system of Grade B - Category LD3 (BS 5839-6: 2004).

 

b. large dwellings of 3 or more storeys (excluding basements) to have fire detection / alarm system of Grade A - Category LD2 (BS 5839-6: 2004).

 

Upgrading of Doors

Any new door forming the protected escape route protection will have to be a FD20 / E20 fire-resistant door fitted in an appropriate frame as recommended by the fire door manufacturer. Intumescent seals may also have to be fitted to the frame or door edges as recommended by the door manufacturer to ensure it achieves the FD20 / E20 rating. You will need to check the installation recommendations on purchase of your fire doors, if in doubt - order the doors with the intumescent seals fitted.

 

Existing doors to all rooms (other than a bathroom, shower-room or w.c.) on the escape route need to be replaced with FD20 / E20 fire doors. This might involve the removal and replacement of door frames to accommodate the thicker fire doors and to achieve the appropriate fire rating standard. Similarly, intumescent seals may also have to be fitted as previously mentioned above.

 

If you wish to consider upgrading the existing doors e.g. they may be of historically or architectural merit, you will be required to upgrade them to an approved method supported by appropriate manufacturers test data and confirmation that the doors meet their upgradeability standards. Note: not all doors can be upgraded as they may be too thin or the infill panels and fixings may be inadequate, so consider the implications carefully if you choose this option.

 

There is no requirement for these fire doors to have self-closers fitted, but if you are a builder or architect you are advised to inform your client of the importance of managing these fire doors and keeping them shut whenever possible.

 

Door hinges may need changing to steel hinges as all hinges on fire doors should have a minimum melting point of 800 degrees C (brass and aluminium hinges will fail prematurely).

 

Any door glazing needs to be 30 minute fire-resistant and of appropriate safety glazing, fixed in accordance with the glazing manufacturer’s requirements to ensure the fire-rating is achieved. This is particularly important if you intend to upgrade existing doors as glazing rebates / beads will likely require improvement or replacement.

 

Protected Escape Route

You need 30-minute fire protection to the escape routes and the walls forming the protected routes need to be carefully checked to see if they will achieve the required fire rating. Masonry walls will achieve the standard, but if they are of stud construction you will be expected to prove that they provide 30 minutes fire-resistance; for instance lath and plaster walls may achieve only approximately 20 minutes fire-resistance and will require upgrading. All new walls will have to be suitably constructed to a full 30-minute fire resistant standard.

 

Ensure all pathways that are likely to bridge the escape route’s fire protection are suitably fire stopped or fire protected (e.g. tops of walls / around services / drainage pipes /air vents etc.)

 

Any glazing that exists in the walls forming the escape route enclosure must be at least 1.1m above the floor level or stair pitch line and changed to 30-minute fire-resistant glass, such as Georgian wired safety glass. If there are existing glazing frames to be adapted, it is likely that they will need replacing to ensure the new fire resisting glass is properly installed in accordance with the manufacturer’s recommendations to achieve the 30-minute fire rating.

 

You must also ensure that any roof spaces that remain over the top of the fire resistant walls are extended up to the underside of the roof covering or, alternatively, a new half hour fire resistant ceiling is provided.

 

The new floor to the loft conversion must be of 30-minute fire-resistant construction i.e. 30 minutes load bearing capacity, 30 minutes integrity and 30 minutes insulation (30/30/30). If you are retaining your existing ceilings, which are usually suspended from the new floor construction, you will have to upgrade any sub-standard ceiling construction to ensure the new floor achieves this required rating.

 

The existing first floor construction would also normally have to be upgraded to a full 30-minute standard construction (which could mean under drawing the existing ceilings). However this can be avoided if the existing floor construction (separating rooms only) is of a ‘modified 30-minute standard’ i.e. reduced performance of 30/15/15, (e.g. 12.5mm plasterboard with joints taped or 9.5mm plasterboard and skim or lath and plaster with 16mm plaster finish over laths), and the following conditions are satisfied:

 

a. Only 1 storey is to be added and the storey contains no more than 2 rooms; and

 

b. The total storey floor area is not more than 50 square metres; and

 

c. Floors which separate rooms from the protected escape route / circulation spaces are upgraded to or achieve a full 30-minute fire resistant standard.

 

Stairs and Headroom Requirements

A fixed staircase complying with approved document K must be installed to form permanent safe access into the converted space.

 

You must have a minimum of 2 metres headroom over the stairs and landings, although a slightly reduced headroom standard of 1.9 metres (to centre-line of stair) can be applied to the stairs where the flight is parallel to the roof slope.

 

Be aware that the space and headroom currently available in the roof space will be considerably reduced by the provision of a new structural floor, the fixed staircase, stair enclosures or guarding and provision of insulation to walls and ceilings etc. You should ensure that the finished space and headroom will make a loft conversion viable before continuing down the design process.

 

Insulation Requirements

Walls, including ashlar walls and dormer cheek walls need to achieve an area-weighted average U-value of 0.28W/m2K.

 

A pitched roof, including pitched dormer roof will need to achieve a U-value of 0.16W/m2K if insulation is installed at ceiling level, or 0.18W/m2K if insulation is installed at rafter level.

 

Flat roofs, including flat dormer roofs, need to achieve a U-value of 0.18W/m2K.

 

The floor construction will need to be insulated to prevent excessive sound transmission to and from rooms below.

 

Other Considerations

Modern houses with trussed rafter roofs are usually unsuitable for loft conversions, as the inner members of the truss cannot normally be removed. You are advised to seek advice of a suitably qualified professional to establish whether or not the roof structure can be altered to accommodate the planned accommodation.

 

The existing ceiling joists in the roof will almost certainly be inadequate for use as floor joists. In most cases it is possible to install new floor joists and support beams between the existing ceiling joists to maximise the headroom available. You are advised to seek professional guidance and provide calculations for any support beams you intend to provide to support the floor.

 

The new rooms will need to be fully insulated to prevent excessive heat loss and sound transmission. While there are many ways of achieving this, we would recommend that you check your chosen method with your Building Control Surveyor before any insulation is installed. Be advised that the provision of this insulation will often reduce the headroom to the existing loft space.

 

You should be aware that the above is guidance only, and there are many other areas where the building regulations impose requirements relating to loft conversions.

 

You are strongly advised due to the complex nature of these types of projects that you make a full plans application, where the majority of the problems can be resolved before you start the works.

This webpage was updated on 1/31/2012

 

Ashford Borough Council, Civic Centre
Tannery Lane, Ashford TN23 1PL
Telephone: 01233 331111
Email: customer.care@ashford.gov.uk or view our contact us page.
Ashford Borough Council Ashford, Best Placed in Britain

More about advertising on our site ...